M6.2 Closed-Loop Time-Domain Simulation
Here, we begin by using the SIMULINK diagram shown in Figure M6-1.

The system is on the verge of instability when kc = 3.8 %/°C, as shown in Figure M6-2; the ultimate proportional gain is then kcu = 3.8 %/°C. The period of oscillation (ultimate period, Pu) is approximately 17.2 minutes. Both of these values can be obtained from frequency-response analysis, as shown in Section M6.3. Notice that the manipulated variable action is constant from t = 1 to t = 6 minutes. This is due to the initial "proportional kick." The manipulated input does not change until the process output is observed to change at t = 6 minutes (remember there is a 5-minute time delay). If we used a controller with integral action, the manipulated input would have kept increasing during this interval.

|